HK INSTRUMENT
DPT-R8
Field adjustable, multi-range differential pressure transmitters for air
DPT-R8 series differential pressure transmitters are engineered for building automation in the HVAC/R industry. The most technologically advanced transmitters on the market measuring static and differential pressure, with field selectable units, range and output, all in a single device.
DPT-R8 series devices include:
• Multiple measurement units, field selectable via jumper, including: inWC, mmWC, Pa, mbar.
• 8 fiel
Technical specifications
Accuracy (from applied pressure):
Models 250 and 2500:
Pressure < 125 Pa = 1 % + ±1 Pa
Pressure > 125 Pa = 1 % + ±2 Pa
Model 7000:
Pressure < 125 Pa = 1.5 % + ±1 Pa
Pressure > 125 Pa = 1.5 % + ±2 Pa
(including: general accuracy, temperature drift, linearity,
hysteresis, long term stability, and repetition error)
Thermal effects:
Temperature compensated across the full spectrum of capability
Overpressure:
Proof pressure: 25 kPa
Burst pressure: 30 kPa
Zero point calibration:
Automatic autozero or manual pushbutton
Response time:
4.0 s or 0.8 s, selectable via jumper
Media compatibility:
Dry air or non-aggressive gases
Measuring units: Pa, kPa, mbar, inchWC, mmWC, psi, selectable via jumper
Measuring element:
MEMS
Environment: Operating temperature: -10...50 °C
Storage temperature: -20...70 °C
Humidity: 0 to 95 % rH, non condensing
Physical
Dimensions: Case: 90.0 x 95.0 x 36.0 mm
Weight: 150 g
Mounting: 2 each 4.3 mm screw holes, one slotted
Materials:
Case: ABS
Lid: PC
Duct connectors: ABS
Tubing: PVC
Protection standard: IP54
Display (Optional)
2-line display (12 characters/line)
Line 1: active measurement
Line 2: units
Electrical connections:
4-screw terminal block Wire: 0.2–1.5 mm2 (12–24 AWG)
Cable entry: M16
Pressure fittings:
Male Ø 5,0 mm and 6,3 mm
+ High pressure
− Low pressure
Electrical
Voltage:
Circuit: 3-wire (V Out, 24 V, GND)
Input: 24 VAC or VDC, ±10 %
Output: 0–10V Power consumption: <1.0 W
Resistance minimum: 1 kΩ
Current:
Circuit: 3-wire (mA Out, 24 V, GND)
Input: 24 VAC or VDC, ±10 %
Output: 4–20 mA
Power consumption: <1.2 W
Maximum load: 500 Ω
Conformance
Meets the requirements for CE marking:
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
WEEE Directive 2012/19/EU
2
3